Avcon Thermal Equipment Trip NVT40FF40
Features :
Isolates the gas pipe line in the event of fire.
Offers high thermal capacity.
Operating Principle :
If
the ambient temperature rises above 100°C during fire, a seal in the
NVT melts & releases a spring which is held by a retaining pin. The
spring presses closing the Mechanism and enters into the seat, sealing
and ensuring that no more gas can pass through the line. This fitting
can withstand temperature of up to 925°C and will hold for a minimum
period of ONE hour.
Application :
Thermal
equipment trips are used in gas installation, upstream of gas inlet
lines, to protect equipments down side in event of a fire. The device
isolates gas pipe line and provides long term protection against
uncontrolled escape of gas and explosion. This unique thermal tripping
shut off for valves comply with the requirements of German Fire System
Ordinance and can be used in compliance with TRGI 86/96.
Specification :
Type : NVT
Size : 40 mm
Technical Specifications | |
Type | NVT |
Size | 40 mm |
Commercials | |
Delivery Period | 8 to 10 working days |
Courier Charges | 50 |